Sunways STH 4–12 kW | HV Series

The Sunways STH 4–12 kW (HT) series are three-phase hybrid inverters designed for commercial to large residential installations that require both on-grid and backup capability. They support high-voltage battery systems (wide battery voltage window), fast UPS switching (<10 ms), and robust overload capability (short-term peak output and long-duration overload modes). With a maximum efficiency up to 98.2%, IP65 protection, and flexible battery communication (CAN / RS485), this series targets hybrid solar + storage systems, small commercial sites, shops/offices and residential projects that may scale by adding parallel units or larger battery banks.

Β 

🌟 Key Features

βœ” Power range (rated):

4 kW β†’ 12 kW (models: 4KTL, 5KTL, 6KTL, 8KTL, 10KTL, 12KTL)

βœ” Max efficiency

up to 98.2%

βœ” Protection

IP65 (outdoor capable)

βœ”Overload

up to 200% backup output (short-term/peak modes noted)

βœ” Battery voltage range

140–750 V (wide HV battery support)

βœ” MPPT

2 MPPTs (2 inputs total) with wide MPPT voltage range (150–850 V or 200–850 V depending on model)

βœ” UPS switching time

< 10 ms (uninterruptible supply)

βœ” Cooling

Natural convection (quiet, <25 dB)

Download Datasheet (PDF)

Model Comparison (Key Ratings)

Model Max DC Input Power (W) Start-up Voltage (V) Max DC Input Voltage (V) Rated DC Input Voltage (V) MPPT Voltage Range (V)
STH-4KTL-HT-P6,4001501,000620150–850
STH-5KTL-HT-P8,0001501,000620150–850
STH-6KTL-HT-P9,6001801,000620200–850
STH-8KTL-HT-P12,8001801,000620200–850
STH-10KTL-HT-P16,0001801,000620200–850
STH-12KTL-HT-P19,2001801,000620200–850

Battery

Battery CommunicationCAN / RS485
Battery Voltage Range140–750 V
Max Charge / Discharge Current25 A / 25 A
Built-in Fuse (Rated Current)63 A

Output (Grid Mode)

Rated Output Power (W) Max Output Power (W) Max Apparent Power (VA) Grid Type Rated Frequency Max Output Current (A)
4,000 β€’ 5,000 β€’ 6,000 β€’ 8,000 β€’ 10,000 β€’ 12,000 4,400 β€’ 5,500 β€’ 6,600 β€’ 8,800 β€’ 11,000 β€’ 13,200 4,400 β€’ 5,500 β€’ 6,600 β€’ 8,800 β€’ 11,000 β€’ 13,200 3L / N / PE, 230/400 V 50 / 60 Hz 6.7 β€’ 8.3 β€’ 10 β€’ 13.3 β€’ 16.5 β€’ 20

Output (Backup Mode)

Rated Backup OutputSame as Grid Output (4 kW β†’ 12 kW)
Max Apparent Backup Power4,400 – 13,200 VA
Peak Output (60 sec)8,000 – 20,000 VA
Peak Output per Phase1,600 – 5,000 VA
UPS Switching Time< 10 ms

Efficiency

Max Efficiency98.1% – 98.2%
Euro Efficiency97.3% – 97.4%
MPPT Efficiency99.9%
Battery Conversion Efficiency97.2% – 97.3%

Protection & General Data

Protection

DC Reverse PolarityIntegrated
Battery Reverse ConnectionIntegrated
Insulation ResistanceIntegrated
DC SwitchOptional
Surge ProtectionIntegrated
Over-TemperatureIntegrated
Residual CurrentIntegrated
Anti-IslandingIntegrated
AC Over-voltageIntegrated
OverloadIntegrated
AC Short-circuitIntegrated

General Data

Dimensions (mm)550 Γ— 410 Γ— 175
Weight26 – 28 kg
Protection DegreeIP65
Night Self-consumption< 15 W
TopologyTransformerless
Operating Temperatureβˆ’30Β°C ~ +60Β°C
Humidity0% – 100%
Operating Altitude4000 m (derating > 3000 m)
CoolingNatural Convection
Noise Level< 25 dB
DisplayOLED & LED
CommunicationWiFi / LAN (Optional)